Coordinating Typical Utility Performance with Automatic Transfer Switch Time
Delays and Devices
Any emergency power system designed
to be automatic must use switching controls capable of monitoring utility
voltage, monitoring generator voltage, controlling one or more contactor
assemblies, and communicating a run signal to the separate control assembly of
an engine generator set. All major US manufacturers of automatic transfer
switches including Onan, ASCO, Kohler, Zenith, Russelectric, Generac, Magnatek,
Westinghouse, Lakeshore, and Square "D" incorporate strikingly similar logic
systems. With all the similarities, operational considerations such as voltage
sensor and time delay adjustments, sequence of operation, and troubleshooting
are simplified. In this page I will discuss features common to most automatic
transfer switches as well as typical commercial power company practices and
equipment.
Commercial Power
Commercial electric power companies,
also referred to as utility companies, share a great many similarities all
across the continental United States. All are connected to the national electric
grid. This allows the companies to import or export electrical power instantly
as the situation demands. Should a power shortage occur in Florida because of a
local generating plant problem, the deficit may be instantly corrected by a
power plant in New York with excess capacity to sell. This interconnected system
requires a high degree of standardization among its subscribers including
voltage, frequency, and circuit protection.
- Standard frequency in the US is 60 HZ
- Common delivery voltages are:
120/240 single phase
120/240
three phase delta
120/208 three phase wye
277/480 three phase
wye
- Common protection devices include:
Re-closers
Circuit
breakers
Fuses
- Transformers and capacitors are used to change and condition voltages as
well as correct power factor
When local electric power problems
arise, the utility will exercise one of many options. Since it has to purchase
energy to make up a shortfall, it may try to stretch its available power. The
utility may use a rolling brown-out during which voltage is reduced over
rotating sections of customer base. It may use a stationary brown-out, or it may
opt for complete outages. All of these affect emergency power systems.
Automatic Transfer Switch Sequence of
Operation
Typically, during a power outage or
brown-out, the utility side undervoltage sensor will sense a loss of
power. This will drop out a normally energized relay to begin the following
sequence of events:
- The time delay on start will begin timing. After 3 to 15 seconds, this
time delay will close a contact that sends a run signal to the control panel
of an engine generator set.
- The engine will start. The engine will be controlled by its own separate
automatic control system.
- After the engine starts, the generator will produce electricity.
- When the electricity produced by the generator is sensed by the emergency
side voltage sensor, the time delay for transfer from normal (utility) to
emergency will begin.
- The time delay for transfer to emergency may be set for up to 180
seconds.
- After the time delay for transfer to emergency times out, a signal is
given to the transfer relay to initiate a transfer.
- The transfer switch main contactor will disconnect from the normal source
and move to a neutral position. (If the automatic transfer switch is
not equipped with a time delay neutral, the contactor continues
straight through to the emergency source.)
- The time delay neutral or programmed transition is engaged once the main
contactor moves to the neutral position. This time delay may be adjusted for
up to 60 seconds.
- After the time delay neutral times out, the main contactor moves on to the
emergency position.
- The system will remain in the emergency mode until the utility restores or
the engine generator set fails.
When the utility side undervoltage
sensor senses that normal utility voltage is restored, it will pick up a relay
which will begin the following sequence of events:
- The time delay, on transfer from emergency to normal, will begin timing.
This may be adjustable up to 30 minutes.
- When the time delay from emergency to normal times out, the main contactor
will disconnect from the emergency source and move to the neutral position.
(If the automatic transfer switch is not equipped with a time delay
neutral, the contactor continues straight through to the normal source.)
- Again, the time delay neutral is engaged, creating a pause in the neutral
position.
- After the time delay neutral times out, the main contactor moves on to the
normal source.
- After the contactor switches the load back to utility, the stop or cool
down timer begins timing. This will keep the engine generator set running for
up to 15 minutes without load.
- After the stop timer times out, the run signal to the engine generator set
control panel is discontinued and the engine will stop.
Controls
- Utility Undervoltage Sensor
- The utility undervoltage sensor monitors the normal utility voltage line
to line. It is connected either directly or through a utility interface board
so that it measures A to Be (for a single phase) or A to B, B to C, and C to A
(for three phase voltage). The utility undervoltage sensor is usually set so
that significane voltage drop in any one phase will initiate the run
sequence.
- The undervoltage sensor will be adjustable for both dropout and pickup
with a voltage differential between the two. This differential is important
because utility voltage frequently varies. If the differential is too close,
the system may cycle unneccesarily.
- For example: Let's say the nominal utility voltage to be monitored is 240
VAC, the dropout voltage is set for 220 VAC, and the pickup voltage is set for
230 VAC. If the utility drops to just below 220 VAC because of a heavy load or
brownout on the utility before the lines reach your facility, and the
generator is brought on line, the utility will have to restore all the way
back up to 230 VAC before the voltage sensor will pick up. This has a
stabilizing effect. It allows the generator to carry the load and avoid
oscillations back to the utility.
- Utility Overvoltage Sensor
- As an option, some automatic transfer switches use a utility overvoltage
sensor. This sensor monitors the commercial power for sustained overvoltage
conditions. If it detects voltage above the user's preset parameters, it will
begin the normal sequence of operation. The emergency power system will remain
on line until the overvoltage condition is corrected.
- Generator Voltage Sensor
- This sensor monitors the generator output. It is designed to allow a
transfer to emergency only after the generator voltage has reached the
appropriate level and become stable. It may also have dropout and pickup
adjustments. It may be identical to the utility voltage sensor.
- Time Delay on Start
- The time delay on start is intended to hold off the beginning of the
transter sequence until after the utility has had a chance to stabilize by
itself. Often a momentary outage will occur and the utility will restore
within a few seconds. When this happens, it may be desirable to prevent the
generator from coming on line unless it is really needed.
- Time delay on start controls may be adjustable up to 15 seconds.
- Time Delay on Transfer to Emergency
- The time delay on transfer to emergency is usually adjustable up to
180 seconds. Its purpose is to allow the engine to run for a while before
assuming the load. This may be considered a warm-up period. It also allows the
utility additional time to stabilize.
- With many automatic transfer switches, if the utility voltage restores
before th transfer to emergency occurs, the system will not transfer to
emergency. Instead, it will go immediately to the stop timer, run for that
time setting, and shut down without having assumed the
load.
Commercial power systems use re-closers as well as
breakers.
Public utilities generate and transmit
electrical power at high voltages. They then use transformers to reduce the
voltages to levels usable to industry and homes. Like any electrical
distribution system, these high-voltage systems must have a method for circuit
protection. High voltage allows a different approach.
When a fault occurs on
a high-voltage system, it is often a squirrel or tree branch touching the line.
High-voltage lines are kept secured from people, pets, and livestock, so when a
fault occurs the utility tries to "burn" it off. This is accomplished with an
automatically closing breaker, or "re-closer." This device will open when a
fault happens on a protected line and remain open for a preset time period,
after which it will close again. The cycle may be repeated up to ten times. The
object is to use the high voltage to burn away the branch or animal causing the
fault. Typically, the re-closer is set to stay open for about ten seconds, cycle
three times, then stay open if the fault has not cleared.
The action of a
re-closer may interfere with timing in the automatic transfer switch. For
example:
- A fault occurs on the commercial power.
- The re-closer opens, causing failure of the utility power.
- In the automatic transfer switch, the utility coltage sensor drops out and
the time delay on start begins to time.
- The time delay on start times out and the engine generator set starts
up.
- Power from the engine generator set becomes available and the generator
voltage sensor picks up. This starts the time delay to emergency timing.
- The re-closer closes after 10 seconds to try to clear the fault; it
cannot, so after 3 seconds it again opens the utility's circuit.
- The time delay on transfer continues to time.
- The re-closer closes to again try to clear the fault. This time the effort
is successful and commercial power is restored.
- With commercial power back on, the utility voltage sensor picks up. This
stops the time delay on transfer to emergency and starts the time delay on
stop.
- After approximately 5 minutes, the time delay on stop times out and the
signal to the engine generator set is discontinued. The engine
stops.
- Time Delay Neutral
- With many automatic transfer switches it is possible to pause the action
of the main contactor, for up to 60 seconds, in the neutral position. This is
desirable in applications involving large motors, compressors (such as air
conditioners), rectifiers, UPS systems, and transformers.
- Many automatic transfer switches will transfer from one source to the
other in less than 250 milliseconds. A pause allows for a smooth transition.
When a pause is not allowed, the rapid transfer from one hot source to the
other hot soure may have the following effects:
- Air conditioners, compressors, mills, or other motors working under a
heavy load with low enertia tend to stall when the contactor disconnects.
When the transfer completes, the motor has difficulty restarting unless the
load is removed. Often, these devices use a time delay relay to allow
compressor pressures to equalize before restarting or motor contactors which
fall out with the loss of voltage and must be manually reset.
- The speed of transfer, however, defeats the built-in safety devices. The
transfer may be so fast that the contactor or time delay relay fails to fall
out before the transfer is complete. In this event, the motor may stall or the
engine generator set may fail to perform adequately due to the extreme
overload.
- Large motors driving heavy inertia loads develop regenerative
voltage when disconnected from a power source. This happens whent he driven
equipment continues to turn the motor by means of inertia. The motor actually
becomes a generator until it is allowed to slow down. A pause in neutral will
allow the regenerative voltage to decay before the connection to the secondary
source is made.
- Rectifiers, UPS systems, and transformers, as an integral part of
their design, use a large coil of wire wrapped around an iron core. When such
a core is energized, an electrical field develops. When the circuit is opened
and the electrical field is allowed to collapse, a high-voltage spike will
develop. This spike must be routed to ground ot be allowed to dissipate if
damage is to be prevented in equipment connected to the circuit. A pause in
neutral allows the spike to dissipate. Whent he transfer is made without
pause, damage to sensitive driven equipment may occur.
- Time Delay from Emergency to Normal
- When the utility side voltage sensor senses the return of commercial
power, the time delay on transfer from emergency to normal will begin timing.
This time delay is adjustable up to 30 minutes. When commercial power
restores, it often takes some time for it to stabilize. This time delay keeps
the load on the generator power until the commercial power has been at the
appropriate level for the duration of the time delay setting.
- Time Delay on Stop
- When an engine runs under load, it builds up heat within the metal of the
block, manifolds, and cylinder head. This head is dissipated through the
cooling system as long as the engine runs, but when the engine stops, the
cooling system stops as well. If excess heat has built up due to heavy load,
it may cause damage to the engine's systems or it may evacuate coolant. This
time delay allows the engine to run without load for up to 15 minutes. The
extended run allows the cooling system to remove the excess heat and thus
minumize the prospect of engine damage.
- Note: Kohler puts its time delay on stop in the engine generator control
panel rather than the automatic transfer switch.
- In-phase Monitor
- Some automatic transfer switches have an in-phase monitor as an option.
The object of this devices is to overlap the phase rotation of he commercial
source with the emergency source. This is an awkward application in that it is
only appropriate where regenerative voltage is possible. Since only large
motors with high-inertia loads and possibly elevators are likely to generate
regenerative voltage, applications for in-phase monitors are limited. However,
we find them installed in many applications. I can only assume the design
engineers or owners failed to understand the function and application of
in-phase monitors.
- When inappropriately applied, an in-phase monitor can cause lots of
trouble. It monitors the phase angle of both sources, and if improperly
adjusted, will prevent a transfer. I recommend that these be taken out of the
control circuit if not needed for a specific purpose.
- Minimum Run Timer
- Generac uses a minimum run timer in its automatic transfer switch. This
timer does not affect the transfer operation. It may be set for up to 30
minutes. Its sole function is to keep the engine generator set running for a
preset period of time once the automatic control issued a run signal. I
recommend this be set for five minutes.
Generator Services, Inc. Recommended Timer Settings:
Time Delay on Start 5-10 Seconds
Time Delay Normal to Emergency 30-60 Seconds
Time Delay Neutral 5 Seconds
Time Delay Emergency to Normal 15 Minutes
Time Delay on Stop 5 Minutes
Minimum Run Timer 5 Minutes
Note: These recommendations are for most applications. Health care,
communications, FCC, FAA, EMS, or other special applications may have different
requirements.
- Automatic Exerciser Clock
- An automatic transfer switch is usually equipped with an exerciser clock
as an option. Many different clocks are used but they generally function the
same way. In the "with load" mode, the clock should engage all the time delays
except possibly the time delay on start. It will often accomplish this by
failing the utility undervoltage sensor. In the "without load" mode it should
only run the engine generator set without transferring the load.
- The clock should be a seven or fourteen day repeatable timer with multiple
settings for the exercise period. I prefer to set the clock for a 15-minute
run "with load." This will engage the time delay on emergency to normal (15
minutes) and the time delay on stop (5 minutes) to give the unit a 35-minute
total exercise run time.
- If the utility fails during an exercise cycle, the automatic controls will
take over to serve the load. If the exerciser clock is set in the "without
load" mode, it will transfer during an outage. The "without load" mode
only affects the exercise cycle.
- Test Switch
- Some automatic transfer switches have a test switch. This may be a toggle
switch, push button, or key-type switch. The "with load" "without load"
controls apply, just like with the exerciser clock mentioned above.
- The automatic transfer switch may be placed in test "with load" mode in
the event a storm or other potential utility interruption is expected. This
will put the emergency power system on line. It may remain on line for the
duration of the event. When the emergency power system is no longer needed,
the test switch may be returned to normal.
Home
Back to
Lester's Science Corner